AIRPAX®
Circuit
Protectors & |
| |
Circuit
Breakers |
|
|
|
 |
IAR Series |
|
 |
SNAPAK® Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker SPST or DPST Toggle, rocker, push-pull, push-to-reset Patented snap action mechanism Illuminated rocker handle |
Max. Poles: |
2
|
Current & Voltage Ratings: |
0.10 to 7.5 amps, 50Vdc & 250VAC
0.10 to 30 amps, 32Vdc
0.10 to 30 amps, 120Vac
0.10 to 25 amps, 120/240Vac (2 poles breaking)
0.10 to 20 amps, 250Vac, 50/60Hz at 500AIC
0.10 to 20 amps, 65Vdc, 500AIC (2 poles breaking)
|
Interrupting Capacity: |
1,000 amps
|
Approvals: |
UL Recognized CSA Certified VDE Approved CCC Approved CE Compliant
|
| |
|
|
 |
UL489A Snapak |
|
 |
|
General Description: |
UL 489A Listed, Snapak circuit breaker, including Rocker, Push-Pull and Push to Reset. |
Max. Poles: |
1
|
Current & Voltage Ratings: |
0.1 - 30 amps, 65VDC, 1000 AIC
0.1 - 30 amps, 80VDC, 600 AIC
|
Interrupting Capacity: |
1000 AIC @ 65VDC
600 AIC @ 80VDC
|
Approvals: |
VDE approved CE compliant UL 489A
|
| |
|
|
 |
AP Series |
|
 |
|
General Description: |
The AP fully sealed, magnetic circuit breaker combines power switching and accurate, reliable circuit protection with inverse time delays and trip free features.
For more info on creating MIL specific part numbers to order, please visit : MIL-PRF-39019 |
Max. Poles: |
3
|
Current & Voltage Ratings: |
AP Ratings:
0.05 to 20 amps, 240Vac, 50 Vdc
UP Ratings:
0.05 to 20 amps at 50Vdc
0.05 to 15 amps at 120Vac
0.05 to 7.5 amps at 240Vac
|
Interrupting Capacity: |
AP Ratings:
500 amps at 50Vdc & 120Vac
300amps at 240Vac
UP Ratings:
1000 amps at 50Vdc & 240Vac
|
Approvals: |
QPL to MIL-PRF-39019 UL Recognized (UP style only)
|
| |
|
|
 |
IAG Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker
Multi-pole versions, multi or single handle
Options: Auxiliary switch, snap-in mounting, mid-trip handle, dual frequency
IEG version meets IEC spacing requirements for installation in equipment that must comply with IEC 601 and 950, and VDE 0730, 0804, and 0805 |
Max. Poles: |
6
|
Current & Voltage Ratings: |
0.05 to 50 amps, 80Vdc
0.05 to 50 amps, 240Vac, 50/60 Hz
0.05 to 30 amps, 277Vac, 50/60 Hz
0.05 to 30 amps, 250Vac, 400 Hz
0.05 to 30 amps, 125Vac, 50/60 Hz (LEG style)
1.0 to 30 amps, 120/240Vac, 50/60 Hz (LEG style)
|
Interrupting Capacity: |
5,000 amps, 240Vac, 50/60 Hz
1,500 amps, 240Vac, 400 Hz
7,500 amps, 80Vdc (IEG)
5,000 amps, 80Vdc (CEG)
2,000 amps, 250Vac, 50/60 Hz (VDE)
4,000 amps, 80Vdc, (VDE)
5,000 amps, 125Vac, 50/60 Hz (LEG style)
5,000 amps, 120/240Vac, 50/60 Hz (LEG style)
|
Approvals: |
UL 489A Listed (CEG) UL Recognized CSA Certified VDE Approved (IEG, CEG) UL 1500 Certified CE Compliant CCC Approved
|
| |
|
|
 |
LEG Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker Multi-pole versions, multi or single handle Options: Auxiliary switch, snap-in mounting, mid-trip handle.
|
Max. Poles: |
2 poles with a max of three sections
|
Current & Voltage Ratings: |
50/60 HZ. 125VAC, .05 - 30 amps
50/60 HZ. 120/240VAC, 1.0 - 30 amps
VDE, 50/60 HZ, 250VAC, .10 - 30 amps
|
Interrupting Capacity: |
5000 AIC. UL listed
2000 AIC. VDE
|
| |
|
|
 |
LEJ Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker 240VAC per pole, 2 poles max, multi or single handle, low-depth "A" option available
|
Max. Poles: |
2
|
| |
|
|
 |
APG Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit protector
QPL to MIL-PRF-55629
Options: Panel seal toggle version, color handles rocker handles
Multi-pole assemblies with single toggle actuation simplifies installation |
Max. Poles: |
4
|
Current & Voltage Ratings: |
0.02 to 30 amps, 277Vac, 65Vdc
0.02 to 50 amps, 250Vac, 65Vdc
|
Interrupting Capacity: |
2,000 amps, 65Vdc
2,100 amps, 250Vac, 400 Hz
5,000 amps, 277Vac, 50/60 Hz
500 amps, 65 Vdc, 250 Vac (VDE)
|
Approvals: |
UL Recognized CSA Certified QPL to MIL-PRF-55629 VDE Approved (IPG) CE Compliant (IPG)
|
| |
|
|
 |
IAL Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit protector
Multi-Pole versions with multi or single handle
Options: Auxiliary switch, snap-in mounting, mid-trip handle, dual frequency
IEL versions meet IEC spacing requirements for installation in equipment that must comply with IEC 601 and 950, and VDE 0730, 0804, and 0805 |
Max. Poles: |
6
|
Current & Voltage Ratings: |
0.05 to 100 amps, 65Vdc
0.05 to 70 amps, 80Vdc
0.05 to 70 amps, 240Vac, 50/60 Hz
0.05 to 50 amps, 277Vac, 50/60 Hz
0.05 to 50 amps, 277/480Vac, 50/60 Hz
0.05 to 50 amps, 250Vac, 400 Hz
|
Interrupting Capacity: |
5,000 amps, 250Vac, 50/60 Hz
1,500 amps, 250Vac, 400 Hz
7,500 amps, 80Vdc
2,000 amps, 240Vac, 50/60 Hz (VDE)
2,000 amps, 415Vac, 50/60 Hz (VDE)
4,000 amps, 80Vdc (VDE)
1,200 amps, 277/480Vac
|
| |
|
|
 |
LEL Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker
Multi-pole versions with multi or single handle
Options: Auxiliary switch, snap-in mounting, mid-trip handle, dual frequency
LEL versions meet IEC spacing requirements for installation in equipment that must comply with IEC 601 and 950, and VDE 0730, 0804, and 0805 |
Max. Poles: |
3
|
Current & Voltage Ratings: |
0.05 to 100 amps, 80Vdc
0.05 to 50 amps, 125Vac, 50/60 Hz
0.05 to 70 amps, 120/240Vac 50/60Hz
0.10 to 100 amps, 80Vdc (VDE)
0.10 to 50 amps, 250Vac (VDE)
|
Interrupting Capacity: |
50,000 amps, 80Vdc
5,000 amps, 125Vac, 120/240Vac, 50/60 Hz
2,000 amps, 80Vdc (VDE)
2,000 amps, 240Vac, 50/60 Hz (VDE)
|
Approvals: |
UL 489 Listed CSA Certified VDE Approved CCC Approved CE Compliant
|
| |
|
|
 |
LELHP & CELHP Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker
Unique, parallel current sensing design
Compact size, high current capacity
Options: Auxiliary switch, mid-trip handle |
Max. Poles: |
1
|
Current & Voltage Ratings: |
125 amps, 80Vdc, paralleled poles
150 amps, 80Vdc, paralleled poles
175 amps, 80Vdc, paralleled poles
200 amps, 80Vdc, paralleled poles
250 amps, 80Vdc, paralleled poles
|
Interrupting Capacity: |
50,000 amps, 80Vdc (up to 100 amps)
50,000 amps, 65Vdc (up to 200 amps)
10,000 amps, 80Vdc (>100 amps)
|
Approvals: |
UL 489 Listed CSA Certified UL 489A Listed CCC Approved
|
| |
|
|
 |
APL Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit protector
QPL to MIL-PRF-55629
Circuit protection with ON-OFF switching
Multi-pole assemblies available with a mix of current ratings, delays and configurations |
Max. Poles: |
9
|
Current & Voltage Ratings: |
0.05 to 20 amps, 277Vac
0.05 to 50 amps, 250Vac
0.05 to 100 amps, 65Vdc
|
Interrupting Capacity: |
5000 amps, 65Vdc (50 amp max. rating)
5000 amps, 120Vac (50 amp max. rating)
5000 amps, 277Vac (20 amp max. rating)
|
Approvals: |
UL Recognized CSA Certified QPL to MIL-PRF-55629 CE Compliant
|
| |
|
|
 |
205 Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit protector
Dust Proof enclosure
Barrier styles available for multi-pole units
Ideal for harsh environments
Tongue and groove construction provides overlapping closure |
Max. Poles: |
9
|
Current & Voltage Ratings: |
0.05 to 30 amps, 277/480Vac
0.05 to 60 amps, 250Vac, 65Vdc
0.05 to 100 amps, 65Vdc
|
Interrupting Capacity: |
5,000 amps, 250Vac, 65Vdc
3,000 amps, 65Vdc
1,500 amps, 277/480Vac (30 amp max.)
5,000 amps, 277/480Vac with 125 amp series fuse
|
Approvals: |
UL Recognized CSA Certified CE Compliant
|
| |
|
|
 |
DPA / DPAP Series |
|
 |
|
General Description: |
|
Max. Poles: |
2
|
Interrupting Capacity: |
1000
|
Approvals: |
no approvals
|
| |
|
|
 |
IPA Series |
|
 |
|
General Description: |
Low-cost, Airpax™ magnetic circuit breaker that combines power switching and accurate, reliable circuit protection for equipment in the international market place. Toggle handle configuration.
Product family: 260 |
Approvals: |
UL recognized CUR recognized TUV approved CE compliant
|
| |
|
|
 |
IELR Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit protector
Designed to mount on standard 35mm DIN rails
IELR versions meet IEC spacing requirements for installation in equipment that must comply with IEC 601 and 950, and VDE 0730, 0804, and 0805 |
Max. Poles: |
4
|
Current & Voltage Ratings: |
0.05 to 70 amps, 80Vdc
0.05 to 70 amps, 250Vac, 50/60 Hz
0.10 to 50 amps, 80Vdc (VDE)
0.10 to 50 amps, 250Vac, 50/60 Hz (VDE)
0.10 to 30 amps, 415Vac, 50/60 Hz (VDE)
|
Interrupting Capacity: |
7,500 amps, 80 Vdc
5,000 amps, 250Vac, 50/60 Hz
2,000 amps, 277Vac, 50/60 Hz
2,000 amps, 250Vac, 50/60 Hz (VDE)
2,000 amps, 415Vac, 50/60 Hz (VDE)
4,000 amps, 80Vdc (VDE)
|
Approvals: |
UL Recognized CSA Certified VDE Approved (IELR) CE Compliant
|
| |
|
|
 |
209 Series (Toggle) |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker
Front-or-back connected terminal styles
Complies with International Requirements
279 style complies to UL 489A
249 Power Selector Breaker System is listed as a Branch Circuit Breaker per UL 489
E-Frame style model complies with UL standard 489 |
Max. Poles: |
6
|
Current & Voltage Ratings: |
0.10 to 100 amps, 160Vdc
0.10 to 100 amps, 125Vdc
0.10 to 77 amps, 600Vac
0.10 to 100 amps, 120, 240, 277, 480Vac
0.10 to 100 amps, 347/600Vac
0.10 to 100 amps, 125Vdc, 240Vac, 240/415Vac (VDE)
|
Interrupting Capacity: |
5,000 amps
10,000 amps
4,000 (VDE)
|
Approvals: |
UL 489 Listed UL 489A Listed (279) UL Recognized CSA Certified VDE Approved UL 1500 Certified CE Compliant
|
| |
|
|
 |
JAE Series |
|
 |
|
General Description: |
Hydraulic-magnetic circuit breaker
F-Frame style complies with UL 489
Various terminal options for design flexibility
Options: Auxiliary switch, mid-trip handle
Reduced voltage drop through the circuit breaker compared to other circuit protective devices |
Max. Poles: |
6
|
Current & Voltage Ratings: |
UL 489:
100 to 250 amps, 160Vdc
100 to 250 amps, 65Vdc
100 to 250 amps, 125/250Vdc (2 poles breaking)
100-250 amps, 240Vac
UL 489A:
275 - 800 amps, (paralleled poles)
275 - 1200 amps, 65Vdc (paralleled poles)
|
Interrupting Capacity: |
10,000 amps, 160Vdc
10,000 amps, 125/250Vdc
50,000 amps, 65Vdc
10,000 amps, 240Vac
18,000 amps, 240Vac
100,000 amps, 65Vdc
(UL 489A, up to 800A)
|
Approvals: |
UL 489 Listed UL 489A Listed UL 1077 Recognized CSA Certified CCC Approved
|
| |
|
|
*Consult
factory for conditions
of acceptability
UL Listed products are deemed
circuit breakers by CSA,
all other products
must be considered